I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here  

Update 1: Since I was asked, here are photos of the meter and the EVSE:

enter image description here enter image description here enter image description here enter image description here enter image description here

Update 2: I moved the meter in a small compartment at the top left, mounted it on a stick-on DIN rail and now I was able to properly put a filler plate. See photos:

enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here  enter image description here enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here

Update 1: Since I was asked, here are photos of the meter and the EVSE:

enter image description here enter image description here enter image description here enter image description here enter image description here

Update 2: I moved the meter in a small compartment at the top left, mounted it on a stick-on DIN rail and now I was able to properly put a filler plate. See photos:

enter image description here enter image description here enter image description here enter image description here

Notice removed Comments only by CommunityBot
Post Unlocked by CommunityBot
Post Locked by Niall C.
Notice added Comments only by Niall C.
Mod Moved Comments To Chat
added 88 characters in body
Source Link
user162793
  • 452
  • 2
  • 15

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

added 85 characters in body
Source Link
user162793
  • 452
  • 2
  • 15

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

I don't have enough clearance to install a filler plate because of a power meter for load shedding EVSE that touches the electrical panel cover. See photos. What other options do I have? Is welding a previously removed twistout an option?

enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here enter image description here

added 85 characters in body
Source Link
FreeMan
  • 48k
  • 25
  • 95
  • 205
Loading
added 85 characters in body
Source Link
user162793
  • 452
  • 2
  • 15
Loading
Added photos of the power meter
Source Link
user162793
  • 452
  • 2
  • 15
Loading
Source Link
user162793
  • 452
  • 2
  • 15
Loading