Most engines don't like to start after extended storage. One cause is a dry cylinder bore which prevents compression.

Solution: pull the spark plug and squirt a generous amount of oil into the cylinder. Like 25% of displacement. Turn the generator so the cylinder is vertical and leave it for a few hours so the oil can flow into the piston grooves. Return it to upright for 30 minutes (so fluids can drain to the proper position).

(Very important)Very important: Cover the spark plug hole with paper towel and crank for 5-10 seconds. A considerable amount of oil should blow out of the plug hole. Now replace the plug and try starting again.

Most engines don't like to start after extended storage. One cause is a dry cylinder bore which prevents compression.

Solution: pull the spark plug and squirt a generous amount of oil into the cylinder. Like 25% of displacement. Turn the generator so the cylinder is vertical and leave it for a few hours so the oil can flow into the piston grooves. Return it to upright for 30 minutes (so fluids can drain to the proper position).

(Very important) Cover the spark plug hole with paper towel and crank for 5-10 seconds. A considerable amount of oil should blow out of the plug hole. Now replace the plug and try starting again.

Most engines don't like to start after extended storage. One cause is a dry cylinder bore which prevents compression.

Solution: pull the spark plug and squirt a generous amount of oil into the cylinder. Like 25% of displacement. Turn the generator so the cylinder is vertical and leave it for a few hours so the oil can flow into the piston grooves. Return it to upright for 30 minutes (so fluids can drain to the proper position).

Very important: Cover the spark plug hole with paper towel and crank for 5-10 seconds. A considerable amount of oil should blow out of the plug hole. Now replace the plug and try starting again.

1
source | link

Most engines don't like to start after extended storage. One cause is a dry cylinder bore which prevents compression.

Solution: pull the spark plug and squirt a generous amount of oil into the cylinder. Like 25% of displacement. Turn the generator so the cylinder is vertical and leave it for a few hours so the oil can flow into the piston grooves. Return it to upright for 30 minutes (so fluids can drain to the proper position).

(Very important) Cover the spark plug hole with paper towel and crank for 5-10 seconds. A considerable amount of oil should blow out of the plug hole. Now replace the plug and try starting again.